Catalog > Consumer Electronics > Power Supplies > UPS Mecer 10000VA 9KW Online UPS 10000VA 9KW Online UPS ME-10000-WPTV Mecer Online UPS 10000VA 9KW, Power Factor:PF0.9, 16x12V9ah Batteries, SNMP Card, 40Hz~70Hz, Output:230Vac(±1%) 45A, Output Overload: 105%-125%, Load Transfer to Bypass Mode AfteR10min (0-30℃) OR 1min (30-40℃), 248x500x616mm, 62.1kg 20,463.00 ZAR inc for 1 Each 0 in Stock Add Specifications, Prices & Availability may change without notice. Images are for illustration purposes only. E&OE Features Higher power density, more power output Wider input range, higher efficiency Ultra low noise, multiple configurable options High quality LCD with wide view Specifications Model : ME-10000-WPTV Dimensions W*D*H(mm) : 248 x 500 x616 Weight(kg) : 62.1 Power Apparent Power(KVA) : 10KVA/ Active power(KW) : 9KW Mains Voltage range : 120Vac-275Vac(phase to phase) Current* : 52.6 A max Frequency range : 40Hz-70Hz Power factor : 0.99 Output Rating Voltage : 230Vac(±1%) Rating Current : 45A Frequency range : 50Hz x (1±1%); Follow main power in phase lock range Power factor : 0.9 Output Overload 105%-125%, load transfer to bypass mode after 10 min (0-30°C) or 1min(30-40°C); 125%-150%,load transfer to bypass mode after 30s; Over 150%, load transfer to bypass after 0.5s Load crest ratio : 3:1( max) THD : <2%( 100% Line load) Enviromental and safety EMC Standard : EN IEC 62040-2:2018 / EN 62040-2:2006 / IEC 62040-2:2016 Safety Standard : EN62040-1:2008+A1:2013 Operation temperature : 0-40 °C Store temperature : -25°C to 55 °C Relative humidity : 20% to 90% Altitude : <1000m *The max current is under 176Vac input, full rating load and empty battery charging. Downloads User Manual - ME-10000-WPTV PDF File 3.58 MB Datasheet - ME-10000-WPTV PDF File 487.78 KB