Catalog > Electro-Mechanical Components > Industrial Automation Modular 40 A Stabilized Power Supply Power Supply 6EP1437-3BA00 SITOP Modular 40 A Stabilized Power Supply Input: 400-500 V 3 AC Output: 24 V DC/40 A 11,913.00 ZAR inc for 1 Each 0 in Stock Add Specifications, Prices & Availability may change without notice. Images are for illustration purposes only. E&OE Specifications input type of the power supply network 3-phase AC supply voltage at AC ● minimum rated value 400 V ● maximum rated value 500 V ● initial value 320 V ● full-scale value 550 V supply voltage at AC Starting from Vin > 340 V wide range input Yes overvoltage overload capability 2.3 × Vin rated, 1.3 ms buffering time for rated value of the output current in the event of power failure minimum 6 ms operating condition of the mains buffering at Vin = 400 V line frequency 50/60 Hz line frequency 47 ... 63 Hz input current ● at rated input voltage 400 V 2.2 A current limitation of inrush current at 25 °C maximum 70 A I2t value maximum 2.8 A²·s fuse protection type none fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) output voltage curve at output Controlled, isolated DC voltage output voltage at DC rated value 24 V output voltage ● at output 1 at DC rated value 24 V output voltage adjustable Yes; via potentiometer adjustable output voltage 24 ... 28.8 V; max. 960 W relative overall tolerance of the voltage 3 % relative control precision of the output voltage ● on slow fluctuation of input voltage 0.1 % ● on slow fluctuation of ohm loading 0.2 % residual ripple ● maximum 100 mV voltage peak ● maximum 200 mV display version for normal operation Green LED for 24 V OK type of signal at output via signaling module (6EP1961-3BA10) behavior of the output voltage when switching on No overshoot of Vout (soft start) response delay maximum 2.5 s voltage increase time of the output voltage ● maximum 500 ms output current ● rated value 40 A ● rated range 0 ... 40 A; +60 ... +70 °C: Derating 2%/K supplied active power typical 960 W short-term overload current ● at short-circuit during operation typical 120 A duration of overloading capability for excess current ● at short-circuit during operation 25 ms constant overload current ● on short-circuiting during the start-up typical 46 A bridging of equipment Yes; switchable characteristic number of parallel-switched equipment resources for increasing the power 2 efficiency efficiency in percent 90 % power loss [W] ● at rated output voltage for rated value of the output current typical 106 W closed-loop control relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 1 % relative control precision of the output voltage load step of resistive load 50/100/50 % typical 2 % setting time ● load step 50 to 100% typical 4 ms ● load step 100 to 50% typical 4 ms setting time ● maximum 10 ms protection and monitoring design of the overvoltage protection < 35 V property of the output short-circuit proof Yes design of short-circuit protection Alternatively, constant current characteristic approx. 46 A or latching shutdown ● typical 46 A enduring short circuit current RMS value ● typical 46 A display version for overload and short circuit LED yellow for ""overload"", LED red for ""latching shutdown"" safety galvanic isolation between input and output Yes galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) operating resource protection class Class I leakage current ● maximum 3.5 mA protection class IP IP20 EMC standard ● for emitted interference EN 55022 Class B ● for mains harmonics limitation EN 61000-3-2 ● for interference immunity EN 61000-6-2 standards, specifications, approvals certificate of suitability ● CE marking Yes ● UL approval Yes; UL-Listed (UL 508), File E197259 ● UKCA marking Yes ● EAC approval Yes ● Regulatory Compliance Mark (RCM) Yes ● NEC Class 2 No ● SEMI F47 Yes type of certification ● CB-certificate No MTBF at 40 °C 485 437 h standards, specifications, approvals hazardous environments certificate of suitability ● IECEx No ● ATEX No ● ULhazloc approval No ● FM registration No standards, specifications, approvals marine classification shipbuilding approval No Marine classification association ● American Bureau of Shipping Europe Ltd. (ABS) No ● French marine classification society (BV) No ● Det Norske Veritas (DNV) No ● Lloyds Register of Shipping (LRS) No standards, specifications, approvals Environmental Product Declaration Environmental Product Declaration Yes global warming potential [CO2 eq] ● total 2 762.3 kg ● during manufacturing 76.5 kg ● during operation 2 684.1 kg ● after end of life 0.64 kg ambient conditions ambient temperature ● during operation 0 ... 70 °C; with natural convection ● during transport -40 ... +85 °C ● during storage -40 ... +85 °C environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation connection method type of electrical connection screw terminal ● at input L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded ● at output +, -: 2 screw terminals each for 0.33 ... 10 mm² ● for auxiliary contacts - mechanical data width × height × depth of the enclosure 240 × 125 × 125 mm installation width × mounting height 240 mm × 225 mm required spacing ● top 50 mm ● bottom 50 mm ● left 0 mm ● right 0 mm fastening method Snaps onto DIN rail EN 60715 35x15 ● DIN-rail mounting Yes ● S7 rail mounting No ● wall mounting No housing can be lined up Yes net weight 3.2 kg