| General technical data |
| type of current for monitoring |
AC and pulse-shaped direct currents (type A) |
| response time maximum |
100 ms |
| product component |
|
| ● input for thermistor connection |
No |
| ● input for analog temperature sensors |
No |
| ● input for ground fault detection |
Yes |
| consumed active power |
0.1 W |
| protection class IP |
IP20 |
| shock resistance according to IEC 60068-2-27 |
15g / 11 ms |
| vibration resistance according to IEC 60068-2-6 |
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| Substance Prohibitance (Date) |
05/01/2012 |
| measurable line frequency initial value |
400 Hz |
| measurable line frequency full-scale value |
16 Hz |
| relative measurement deviation of residual current transformer |
2.5 % |
| Electromagnetic compatibility |
| EMC emitted interference according to IEC 60947-1 |
class A |
| EMC immunity according to IEC 60947-1 |
corresponds to degree of severity 3 |
| conducted interference |
|
| ● due to burst according to IEC 61000-4-4 |
1 kV |
| ● due to conductor-earth surge according to IEC 61000-4-5 |
2 kV |
| ● due to conductor-conductor surge according to IEC 61000-4-5 |
1 kV |
| ● due to high-frequency radiation according to IEC 61000-4-6 |
10 V |
| field-based interference according to IEC 61000-4-3 |
10 V/m |
| electrostatic discharge according to IEC 61000-4-2 |
6 kV contact discharge / 8 kV air discharge |
| field-bound HF interference emission according to CISPR11 |
corresponds to degree of severity A |
| Inputs/ Outputs |
| number of inputs |
1 |
| number of digital inputs |
0 |
| number of analog inputs |
1 |
| number of sensor inputs for ground fault detection |
1 |
| number of outputs |
0 |
| number of semiconductor outputs |
0 |
| number of outputs as contact-affected switching element |
0 |
| number of analog outputs |
0 |
| Installation/ mounting/ dimensions |
| mounting position |
any |
| fastening method |
screw and snap-on mounting |
| height |
92 mm |
| width |
22.5 mm |
| depth |
124 mm |
| required spacing |
|
| ● top |
40 mm |
| ● bottom |
40 mm |
| ● left |
0 mm |
| ● right |
0 mm |
| diameter of inlet opening of connectable residual current transformer |
35 ... 210 mm |
| Connections/ Terminals |
| type of connectable conductor cross-sections |
|
| ● solid |
1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| ● finely stranded with core end processing |
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| ● at AWG cables solid |
1x (20 ... 14), 2x (20 ... 16) |
| ● at AWG cables stranded |
1x (20 ... 12), 2x (20 ... 14) |
| tightening torque with screw-type terminals |
0.8 ... 1.2 N·m |
| tightening torque [lbf·in] with screw-type terminals |
7 ... 10.3 lbf·in |
| Ambient conditions |
| installation altitude at height above sea level |
|
| ● 1 maximum |
2 000 m |
| ● 2 maximum |
3 000 m; max. +50 °C (no protective separation) |
| ● 3 maximum |
4 000 m; max. +40 °C (no protective separation) |
| ambient temperature |
|
| ● during operation |
-25 ... +60 °C |
| ● during storage |
-40 ... +80 °C |
| ● during transport |
-40 ... +80 °C |
| environmental category |
|
| ● during operation according to IEC 60721 |
3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
| ● during storage according to IEC 60721 |
1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
| ● during transport according to IEC 60721 |
2K2, 2C1, 2S1, 2M2 |
| relative humidity during operation |
5 ... 95 % |
| Safety related data |
| touch protection against electrical shock |
finger-safe |