Call Us Now !
Fluke 393FC Clamp Meter TRUE-RMS 1000VAC CATIII 1500V with IFLEX Current Probe up to 2500A & MC4 Test Lead, IP54 [FLUKE 393FC/PVLEAD]
Fluke 393FC Clamp Meter TRUE-RMS 1000VAC CATIII 1500V with IFLEX Current Probe up to 2500A & MC4 Test Lead, IP54 [FLUKE 393FC/PVLEAD] Fluke 393FC Clamp Meter TRUE-RMS 1000VAC CATIII 1500V with IFLEX Current Probe up to 2500A & MC4 Test Lead, IP54 [FLUKE 393FC/PVLEAD] Fluke 393FC Clamp Meter TRUE-RMS 1000VAC CATIII 1500V with IFLEX Current Probe up to 2500A & MC4 Test Lead, IP54 [FLUKE 393FC/PVLEAD]

393FC Clamp Meter

TRUE-RMS Clamp Meter
Fluke 393FC Clamp Meter TRUE-RMS 1000VAC CATIII 1500V with IFLEX Current Probe up to 2500A & MC4 Test Lead, IP54
Part No: FLUKE 393FC/PVLEAD
23 833.75 ZAR
inc
for 1 Each
Specifications, Prices & Availability may change without notice. Images are for illustration purposes only. E&OE

Overview

The 393 FC CAT III 1500 V True-rms Clamp Meter with iFlex is an industrial clamp meter designed for solar photovoltaic (PV) installation technicians and maintenance professionals who work in high voltage dc environments. Safely connect the Solar PV test leads to the clamp meter to validate voltage and current from individual panels or a series of panels in a PV array. The inline capabilities of the Solar PV PVLEAD3 leads allow the system to remain online and generating power while testing without needing to pierce the line.

Features

  • Measure safely with CAT III 1500 V rated clamp meter
  • Thin jaw for access to cables in crowded combiner boxes
  • Sturdy IP54 rated for outdoor use and solar arrays
  • Work efficiently with dc power measurement, audio polarity and visual continuity
  • Solar PV test lead sets are designed for use with solar clamp meters that accept 4mm banana plugs, rated to CAT III 1000 V / CAT IV 600 V

Specifications

General      
Maximum voltage between any Terminal and Earth Ground    
AC 1000 V    
DC 1500 V    
Batteries 2 AA IEC LR6 alkaline    
Display Dual display with backlight    
Automatic Power Off 20 minutes    
Electrical      
Accuracy      
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]).
Temperature Coefficients Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw      
Range 999.9 A    
Resolution 0.1 A    
Accuracy 2 % + 5 digits (10 Hz to 100 Hz)  
  2.5 % + 5 digits (100 Hz to 500 Hz)  
Crest Factor (50/60 Hz) 2.5 @600.0 A    
  3.0 @500.0 A    
  1.42 @999.9 A    
  Add 2 % for C.F. >2    
AC Current: Flexible Current Probe      
Range 999.9 A    
  2500 A    
Resolution 0.1 A (≤999.9 A)    
  1 A (≤2500 A)    
Accuracy 3 % RD + 5 digits (10 Hz to 500 Hz)  
Crest Factor (50/60Hz) 2.5 @1400 A    
  3.0 @1100 A    
  1.42@2500 A    
  Add 2 % for C.F. >2    
Position Sensitivity      
Distance from Optimum i2500-10 Flex i2500-18 Flex Error
A 0.5 in (12.7 mm) 1.4 in (35.6 mm) ±0.5 %
B 0.8 in (20.3 mm) 2.0 in (50.8 mm) ±1.0 %
C 1.4 in (35.6 mm) 2.5 in (63.5 mm) ±2.0 %
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
       
DC Current      
Range 999.9 A    
Resolution 0.1 A    
Accuracy 2 % RD + 5 digits[1]    
  [1] When using the ZERO (B) function to compensate for offsets.
AC Voltage      
Range 600.0 V    
  1000 V    
Resolution 0.1 V (≤600.0 V)    
  1 V (≤1000 V)    
Accuracy 1 % RD + 5 digits (20 Hz to 500 Hz)  
DC Voltage      
Range 600.0 V    
  1500 V    
Resolution 0.1 V (≤600.0 V)    
  1 V (≤1500 V)    
Accuracy 1 % RD + 5 digits    
mV dc      
Range 500.0 mV    
Resolution 0.1 mV    
Accuracy 1 % RD + 5 digits    
Amps Frequency: Jaw      
Range 5.0 Hz to 500.0 Hz    
Resolution 0.1 Hz    
Accuracy 0.5 % RD + 5 digits    
Trigger Level 5 Hz to 10 Hz, ≥10 A    
  10 Hz to 100 Hz, ≥5 A    
  100 Hz to 500 Hz, ≥10 A    
Amps Frequency: Flexible Current Probe      
Range 5.0 Hz to 500.0 Hz    
Resolution 0.1 Hz    
Accuracy 0.5 % RD + 5 digits    
Trigger Level 5 Hz to 20 Hz, ≥25 A    
  20 Hz to 100 Hz, ≥20 A    
  100 Hz to 500 Hz, ≥25 A    
Voltage Frequency      
Range 5.0 Hz to 500.0 Hz    
Resolution 0.1 Hz    
Accuracy 0.5 % RD + 5 digits    
Trigger Level 5 Hz to 20 Hz, ≥5 V    
  20 Hz to 100 Hz, ≥5 V    
  100 Hz to 500 Hz, ≥10 V    
DC Power      
Range 600.0 kVA (600.0 V dc range)    
  1500 kVA (1500 V dc range)    
Resolution 0.1 kVA    
  1 kVA    
Accuracy 2 % RD + 2.0 kVA    
  2 % RD + 20 kVA    
Resistance      
Range 600.0 Ω    
  6000 Ω    
  60.00 kΩ    
Resolution 0.1 Ω (≤600.0 Ω)    
  1 Ω (≤6000 Ω)    
  0.01 kΩ (≤60.00 kΩ)    
Accuracy 1 % RD + 5 digits    
Capacitance      
Range 100.0 μF    
  1000 μF    
Resolution 0.1 μF (≤100.0 μF)    
  1 μF (≤1000 μF)    
Accuracy 1 % RD + 5 digits    
Inrush Trigger Level 5 A    
Mechanical      
Size (L x W x H) 281 mm x 84 mm x 49 mm    
Weight (with batteries) 520 g    
Jaw Opening 34 mm    
Flexible Current Probe Diameter 7.5 mm    
Flexible Current Probe Cable Length      
(head to electronics connector) 1.8 m    
Environmental      
Operating Temperature -10 °C to 50 °C    
Storage Temperature -40 °C to 60 °C    
Operating Humidity Non condensing (<10°C)    
  ≤90 % RH (at 10 °C to 30 °C)    
  ≤75 % RH (at 30 °C to 40 °C)    
  ≤45 % RH (at 40 °C to 50 °C)    
Operating Altitude 2000 m    
Storage Altitude 12 000 m    
Ingress Protection (IP) Rating IEC 60529: IP54 non-operating    
Electromagnetic Compatibility (EMC)      
International IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11: Group 1, Class A
  Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.
Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
  Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Safety      
General IEC 61010-1, Pollution Degree 2  
Measurement IEC 61010-2-032: CAT III 1500 V / CAT IV 600 V  
  IEC 61010-2-033: CAT III 1500 V / CAT IV 600 V  
Wireless Radio      
Radio frequency certification FCC ID: T68-FBLE, IC: 6627A-FBLE  
Wireless Radio Frequency Range 2400 MHz to 2483.5 MHz    
Output Power <100 mW    
SIMPLIFIED EU DECLARATION OF CONFORMITY    
Hereby, Fluke declares that the radio equipment contained in this Product is in compliance with Directive 2014/53/EU.
The full text of the EU declaration is available at the following Internet address:

Additional Information

Brand Fluke

Downloads


Copyright © 2025, Communica (Pty) Ltd.

Communica is a wholesale and retail distributor of semiconductors, electromechanical and passive electronic components for automotives, electronics, electrical, automation, mining and process control industries and technical and tertiary educational institutions. We also offer a large range of security and CCTV equipment, power supplies, test instruments and accessories, tools and production equipment, prototyping platforms, and hobby and educational products.