Protection type |
Overvoltage protection on output (+/- 30 V) Reverse polarity protection on power supply Short-circuit protection on output Reverse polarity protection on output |
abnormal analogue output voltage |
-15...-11 V when no input or input wire broken 11...15 V when no input or input wire broken |
abnormal analogue output current |
-30…0 mA when no input or input wire broken 22…30 mA when no input or input wire broken |
[Us] rated supply voltage |
24 V DC non isolated +/- 20 % |
Current consumption |
<= 40 mA for voltage output <= 60 mA for current output |
Local signalling |
LED (green) for power ON |
Measurement error |
+/- 0.5 % of full scale (3 or 4 wires) at 20 °C +/- 1 % of full scale (2 wires) at 20 °C +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m) |
Repeat accuracy |
+/- 0.2 % full scale at 20 °C +/- 0.6 % full scale at 60 °C |
Temperature coefficient |
150 ppm/°C |
Maximum wiring resistance |
0.2 Ohm connection in 2 wires |
clamping connection capacity |
2 x 1.5 mm² 1 x 2.5 mm² |
tightening torque |
0.6…1.1 N.m |
Marking |
CE |
Surge withstand |
0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5 |
[Ui] rated insulation voltage |
2000 V |
Fixing mode |
Clip-on (35 mm symmetrical DIN rail) Fixed (mounting plate) |
Safety reliability data |
MTTFd = 43.9 years B10d = 40564 |
Net weight |
0.12 kg |