Basic unit SIMOCODE pro C, PROFIBUS DP interface 12 Mbit/s, RS 485, 4I/3O freely parameterizable, Us: 110...240 V AC/DC, input for thermistor connection Monostable relay outputs |
product brand name |
SIRIUS |
product designation |
Motor management system |
design of the product |
basic unit 1 |
product type designation |
SIMOCODE pro C |
General technical data |
product function |
|
● bus communication |
Yes |
● data acquisition function |
Yes |
● diagnostics function |
Yes |
● password protection |
Yes |
● test function |
Yes |
● maintenance function |
Yes |
product component |
|
● input for thermistor connection |
Yes |
● digital input |
Yes |
● input for analog temperature sensors |
No |
● input for ground fault detection |
No |
● relay output |
Yes |
product extension |
|
● temperature monitoring module |
No |
● current measuring module |
Yes |
● current/voltage measuring module |
No |
● fail-safe digital I/O module |
No |
● ground-fault monitoring module |
No |
● control unit with display |
No |
● control unit |
Yes |
● analog I/O module |
No |
apparent power consumption |
5.3 VA |
consumed active power |
2.9 W |
insulation voltage with degree of pollution 3 at AC rated value |
300 V |
surge voltage resistance rated value |
4 000 V |
protection class IP |
IP20 |
shock resistance |
|
● according to IEC 60068-2-27 |
15g / 11 ms |
|
|
● vibration resistance |
1-6 Hz / 15 mm; 6-500 Hz / 2 g |
switching capacity current of the NO contacts of the relay outputs at AC-15 |
|
● at 24 V |
6 A |
● at 120 V |
6 A |
● at 230 V |
3 A |
switching capacity current of the NO contacts of the relay outputs at DC-13 |
|
● at 24 V |
2 A |
● at 60 V |
0.55 A |
● at 125 V |
0.25 A |
mechanical service life (switching cycles) typical |
10 000 000 |
electrical endurance (switching cycles) typical |
100 000 |
buffering time in the event of power failure |
0.05 s |
reference code according to IEC 81346-2 |
F |
continuous current of the NO contacts of the relay outputs |
|
● at 50 °C |
6 A |
● at 60 °C |
5 A |
type of input characteristic |
Type 1 in accordance with EN 61131-2 |
Substance Prohibitance (Date) |
05/01/2012 |
certificate of suitability |
|
● according to ATEX directive 2014/34/EU |
BVS 06 ATEX F001 |
explosion device group and category according to ATEX directive 2014/34/EU |
II (2) G, II (2 ) D, I (M2) |
Electromagnetic compatibility |
EMC emitted interference according to IEC 60947-1 |
class A |
EMC immunity according to IEC 60947-1 |
corresponds to degree of severity 3 |
conducted interference |
|
● due to burst according to IEC 61000-4-4 |
2 kV (power ports) / 1 kV (signal ports) |
● due to conductor-earth surge according to IEC 61000-4-5 |
2 kV |
● due to conductor-conductor surge according to IEC 61000-4-5 |
1 kV |
● due to high-frequency radiation according to IEC 61000-4-6 |
10 V |
field-based interference according to IEC 61000-4-3 |
10 V/m |
electrostatic discharge according to IEC 61000-4-2 |
6 kV contact discharge / 8 kV air discharge |
conducted HF interference emissions according to CISPR11 |
corresponds to degree of severity A |
field-bound HF interference emission according to CISPR11 |
corresponds to degree of severity A |
Inputs/ Outputs |
product function |
|
● parameterizable inputs |
Yes |
● parameterizable outputs |
Yes |
number of inputs |
4 |
● for thermistor connection |
1 |
number of digital inputs with a common reference potential |
4 |
digital input version type 1 acc. to IEC 61131 |
Yes |
input voltage at digital input at DC rated value |
24 V |
number of outputs |
3 |
number of semiconductor outputs |
0 |
number of outputs as contact-affected switching element |
3 |
switching behavior |
monostable |
type of relay outputs |
Monostable |
wire length for digital signals maximum |
300 m |
wire length for thermistor connection |
|
● with conductor cross-section = 0.5 mm² maximum |
50 m |
● with conductor cross-section = 1.5 mm² maximum |
150 m |
● with conductor cross-section = 2.5 mm² maximum |
250 m |
Protective and monitoring functions |
product function |
|
● asymmetry detection |
Yes |
● blocking current evaluation |
Yes |
● power factor monitoring |
No |
● ground fault detection |
Yes |
● phase failure detection |
Yes |
● phase sequence recognition |
No |
● voltage detection |
No |
● monitoring of number of start operations |
Yes |
● overvoltage detection |
No |
● overcurrent detection 1 phase |
Yes |
● undervoltage detection |
No |
● undercurrent detection 1 phase |
Yes |
● active power monitoring |
No |
product function |
|
● current detection |
Yes |
● overload protection |
Yes |
● evaluation of thermistor motor protection |
Yes |
total cold resistance number of sensors in series maximum |
1.5 kΩ |
response value of thermoresistor |
3 400 ... 3 800 Ω |
● of the short-circuit control |
9 Ω |
release value of thermoresistor |
1 500 ... 1 650 Ω |
Motor control functions |
product function |
|
● parameterizable overload relay |
Yes |
● circuit breaker control |
Yes |
● direct start |
Yes |
● reverse starting |
Yes |
● star-delta circuit |
No |
● star-delta reversing circuit |
No |
● Dahlander circuit |
No |
● Dahlander reversing circuit |
No |
● pole-changing switch circuit |
No |
● pole-changing switch reversing circuit |
No |
● slide control |
No |
● valve control |
No |
Communication/ Protocol |
|
|
● protocol is supported PROFIBUS DP protocol |
Yes |
● protocol is supported PROFINET IO protocol |
No |
● protocol is supported PROFIsafe protocol |
No |
● protocol is supported Modbus RTU |
No |
● protocol is supported EtherNet/IP |
No |
● protocol is supported OPC UA Server |
No |
● protocol is supported LLDP |
No |
● protocol is supported Address Resolution Protocol (ARP) |
No |
● protocol is supported SNMP |
No |
● protocol is supported HTTPS |
No |
● protocol is supported NTP |
No |
● protocol is supported Media Redundancy Protocol (MRP) |
No |
● product function is supported Device Level Ring (DLR) |
No |
number of interfaces |
|
● according to PROFINET |
0 |
● according to PROFIBUS |
1 |
● according to Ethernet/IP |
0 |
product function |
|
● web server |
No |
● shared device |
No |
● at the Ethernet interface Autocrossover |
No |
● at the Ethernet interface Autonegotiation |
No |
● at the Ethernet interface Autosensing |
No |
● is supported PROFINET system redundancy |
No |
● supports PROFIenergy measured values |
No |
● supports PROFIenergy shutdown |
No |
transfer rate maximum |
12 Mbit/s |
identification & maintenance function |
|
● I&M0 - device-specific information |
Yes |
● I&M1 – higher level designation/location designation |
Yes |
● I&M2 - installation date |
Yes |
● I&M3 - comment |
Yes |
type of electrical connection of the communication interface |
9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit) |
Installation/ mounting/ dimensions |
mounting position |
any |
fastening method |
screw and snap-on mounting |
height |
111 mm |
width |
45 mm |
depth |
95 mm |
required spacing |
|
● top |
40 mm |
● bottom |
40 mm |
● left |
0 mm |
● right |
0 mm |
Connections/ Terminals |
product component removable terminal for auxiliary and control circuit |
Yes |
type of connectable conductor cross-sections |
|
● solid |
1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
● finely stranded with core end processing |
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
● at AWG cables solid |
1x (20 ... 12), 2x (20 ... 14) |
● at AWG cables stranded |
1x (20 ... 14), 2x (20 ... 16) |
tightening torque with screw-type terminals |
0.8 ... 1.2 N·m |
tightening torque [lbf·in] with screw-type terminals |
7 ... 10.3 lbf·in |
type of connectable conductor cross-sections for PROFIBUS wire |
2x 0.34 mm², AWG 22 |
Ambient conditions |
installation altitude at height above sea level |
|
● 1 maximum |
2 000 m |
● 2 maximum |
3 000 m; max. +50 °C (no protective separation) |
● 3 maximum |
4 000 m; max. +40 °C (no protective separation) |
ambient temperature |
|
● during operation |
-25 ... +60 °C |
● during storage |
-40 ... +80 °C |
● during transport |
-40 ... +80 °C |
environmental category |
|
● during operation according to IEC 60721 |
3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
● during storage according to IEC 60721 |
1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
● during transport according to IEC 60721 |
2K2, 2C1, 2S1, 2M2 |
relative humidity |
|
● during operation |
5 ... 95 % |
contact rating of auxiliary contacts according to UL |
B300 / R300 |
Short-circuit protection |
design of short-circuit protection per output |
Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A) |
Safety related data |
touch protection against electrical shock |
finger-safe |
Galvanic isolation |
(electrically) protective separation according to IEC 60947-1 |
All circuits with protective separation (double creepage paths and clearances), the information in the "Protective Separation" test report, No. A0258, must be observed (link see further information) |
Control circuit/ Control |
product function soft starter control |
No |
type of voltage of the control supply voltage |
AC/DC |
control supply voltage at AC |
|
● at 50 Hz rated value |
110 ... 240 V |
● at 60 Hz rated value |
110 ... 240 V |
control supply voltage frequency |
|
● 1 rated value |
50 Hz |
● 2 rated value |
60 Hz |
relative symmetrical tolerance of the control supply voltage frequency |
5 % |
control supply voltage at DC |
|
● rated value |
110 ... 240 V |
operating range factor control supply voltage rated value at DC |
|
● initial value |
0.85 |
● full-scale value |
1.1 |
operating range factor control supply voltage rated value at AC at 50 Hz |
|
● initial value |
0.85 |
● full-scale value |
1.1 |
operating range factor control supply voltage rated value at AC at 60 Hz |
|
● initial value |
0.85 |
● full-scale value |
1.1 |
inrush current peak |
|
● at 240 V |
3 A |
duration of inrush current peak |
|
● at 240 V |
1 ms |