Battery Type
|
RITAR Valve Regulated Lead Acid (VRLA)
|
|
Cells Per Unit
|
6
|
|
Voltage Per Unit
|
12 V
|
|
Nominal Capacity
|
12 Ah @ 20-hour rate to 1.75 V/cell @ 25°C
|
|
C3 Capacity
|
9.31 Ah
|
|
C5 Capacity
|
10.5 Ah
|
|
C10 Capacity
|
11.3 Ah
|
|
C20 Capacity
|
12.1 Ah
|
|
Weight
|
Approx. 3.60 kg (Tolerance ±4.0%)
|
|
Max. Discharge Current
|
120 A (5 sec)
|
|
Short Circuit Current
|
590 A
|
|
Internal Resistance
|
Approx. 16.5 mΩ
|
|
Terminal
|
F1/F2
|
|
Recommended Maximum Charging Current
|
3.6 A
|
|
Container Material
|
A.B.S. UL94-HB; UL94-V0 optional
|
|
Operating Temperature – Discharge
|
-20°C to 60°C
|
|
Operating Temperature – Charge
|
0°C to 50°C
|
|
Storage Temperature
|
-20°C to 60°C
|
|
Normal Operating Temperature
|
25°C ±5°C
|
|
Standby Use Voltage
|
13.7 V to 13.9 V @ 25°C
|
|
Cycle Use Voltage
|
14.6 V to 14.8 V @ 25°C
|
|
Temperature Compensation – Standby
|
-3 mV/°C/Cell
|
|
Temperature Compensation – Cycle Use
|
-4 mV/°C/Cell
|
|
Self-Discharge
|
Less than 3% per month @ 25°C
|
|
Storage Before Recharge
|
Up to 6 months @ 25°C; recharge recommended afterward
|
|
Design Life
|
6–8 years (Float charging)
|
|
Battery Type
|
Sealed Valve Regulated Lead Acid (VRLA)
|