Specifications

Supply voltage

  • Load voltage L+
  • Rated value (DC) : 24 V
  • Reverse polarity protection : Yes

Input current

  • from load voltage L+ (without load), max. : 20 mA
  • from backplane bus 5 V DC, max. : 120 mA

Output voltage

  • Power supply to the transmitters
    • present : Yes
    • Rated value (DC) : 24 V
    • short-circuit proof : Yes

Power losses

  • Power loss, typ. : 1.5 W

Analog inputs

  • Number of analog inputs : 8
  • permissible input current for current input (destruction limit), max. : 40 mA

Input ranges

  • Voltage : No
  • Current : Yes
  • Thermocouple : No
  • Resistance thermometer : No
  • Resistance : No

Input ranges (rated values), currents

  • 0 to 20 mA : Yes
  • Input resistance (0 to 20 mA) : 240 Ω
  • Input resistance (-20 to +20 mA) : 240 Ω
  • Input resistance (4 to 20 mA) : 240 Ω

Cable length

  • Cable length, shielded, max. : 800 m

Analog value creation

  • Measurement principle : Sigma Delta

Integrations and conversion time/ resolution per channel

  • Resolution with overrange (bit including sign), max. : 16 bit
  • Integration time, parameterizable : Yes
  • Integration time, ms : 20 ms@50 Hz/16.6 ms@60 Hz/100 ms@100 Hz
  • Basic conversion time, including integration time, ms : 65ms@50Hz / 55ms@60Hz / 305ms@100Hz

Encoder

  • Connection of signal encoders
    • for current measurement as 2-wire transducer : Yes
    • for current measurement as 4-wire transducer : Yes

Errors/accuracies

  • Linearity error (relative to input area) : +/- 0.01 %
  • Temperature error (relative to input area) : +/- 0.001 %/K
  • Crosstalk between the inputs, min. : 70 dB
  • Repeat accuracy in settled status at 25 °C (relative to input area) : +/- 0.1 %

Operational limit in overall temperature range

  • Current, relative to input area : +/- 0,15 %

Basic error limit (operational limit at 25 °C)

  • Current, relative to input area : +/- 0,1 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min. : 40 dB
  • Common mode interference, min. : 100 dB

Isochronous mode

  • Isochronous operation (application synchronized up to terminal) : No

Downloads

PDF File
117.77 KB

Copyright © 2024, Communica (Pty) Ltd.

Communica is a wholesale and retail distributor of semiconductors, electromechanical and passive electronic components for automotives, electronics, electrical, automation, mining and process control industries and technical and tertiary educational institutions. We also offer a large range of security and CCTV equipment, power supplies, test instruments and accessories, tools and production equipment, prototyping platforms, and hobby and educational products.